Jump to the main text


| Model |
40ASC-H(Z) |
50ASC-H(Z) |
60ASC-H(Z) |
Overall dimensions
mm(inch) |
Height |
562(22-1/8) |
| Width |
585.5(23) |
595(23-7/16) |
600(23-5/8) |
| Length |
840(33-1/8) |
874(34-7/16) |
938(36-15/16) |
| Net Weight |
kg(lbs) |
400(882) |
440(970) |
460(1,014) |
Piping connections
mm(inch) |
Suction |
60.5(2-3/8) |
| Discharge |
48.6(1-7/8) |
| Oil Charge |
liter |
6.0 |
| Frequency |
Hz |
50 |
60 |
50 |
60 |
50 |
60 |
Cooling
Capacity
(R407C) |
kW (×1000Btu/h) |
121.7
(415.3) |
146.7
(500.6) |
150.2
(512.5) |
180.9
(617.3) |
184.9
(630.9) |
222.8
(760.2) |
| Motor input |
kW |
30.1 |
36.3 |
37.2 |
44.8 |
45.8 |
55.2 |
| Displacement |
m3/h |
137.4 |
165.6 |
169.5 |
204.2 |
208.7 |
251.5 |
| Saturated Discharge (Condensing) Temperature |
54.4 (130 ) |
| Subcooled (Liquid) Temperature |
40.6 (105 ) |
| Saturated Suction (Evaporator) Temperature |
4.4 (40 ) |
| Return Gas Temperature |
12.8 (55 ) |
- The compressors are driven by a two pole motor directly mounted on the compressor shaft. A rotation speed at 50Hz is 2,880 rpm and that at 60Hz is 3,470 rpm respectively at a rated voltage.
- Either refrigerant of R407C, R134a or R22 is applicable. Oil is charged in each compressor at the time of shipment.
- Models of 40ASC-H, 50ASC-H and 60ASC-H are designed for STEP capacity control system.
The capacity shall be set at either 100%, 75%, 50% or 15% (for all models).
- Models of 40ASC-Z, 50ASC-Z and 60ASC-Z are designed for INFINITE capacity controll system.
The capacity range is between 100% and 15% (for all models).
- Piping sizes show the external diameter of pipe connection of pre-equipped flange in "mm".
- The standard color is light green (Munsell code 10G 5/2). Other colors are available upon request.
- The cooling capacity and the motor input are based on the following conditions,
ARI Standard rating conditions for compressors used in Air Conditioners and Heat Pumps.
- The overall dimensions and the net weight are subject to change depending on order specifications.
- These Compressors should be installed indoors or in a location equivalent to an indoor environment.
| Model |
4005SC-H(Z) |
5005SC-H(Z) |
6005SC-H / 6005SC-Z |
Overall
dimensions
mm(inch) |
Height |
505(19-7/8) |
530(20-7/8) |
| Width |
413(16-1/4) |
458(18) |
| Length |
1,093(43) |
1,179(46-3/8) |
1,209(47-5/8) |
| Net Weight |
kg(lbs) |
360(794) |
420(926) |
440(970) |
Piping
connections
(mm) |
Suction O.D. |
60.5 |
| Discharge O.D. |
42.7 |
48.6 |
| Oil Charge |
liter |
6.0 |
| Frequency |
Hz |
50 |
60 |
50 |
60 |
50 |
60 |
Cooling Capacity
(R22) |
kW (×1000Btu/h) |
132.2
(451.1) |
159.6
(544.6) |
163.8
(558.9) |
196.9
(671.9) |
201.7
(688.2) |
242.6
(827.8) |
| Motor input |
kW |
32.5 |
39.0 |
40.0 |
48.0 |
49.5 |
59.5 |
| Displacement |
m3/h |
137.4 |
165.6 |
169.5 |
204.2 |
208.7 |
251.5 |
| Condensing Temperature |
40.6 (105 ) |
| Leaving Liquid Temperature |
40.6 (105 ) |
| Evaporating temperature |
4.4 (40 ) |
| Suction Gas Temperature to Compressor |
12.8 (55 ) |
- The compressors are driven by two pole motors directly mounted on the compressors
shaft, and with a rotation of 2,880 rpm for 50Hz and 3,470 rpm for 60Hz, at
the rated voltage.
- Refrigerant R22, R407C and R134a are applicable to these compressors. Oil
is charged in these compressors at the time of shipment.
- Models of 4005SC-H, 5005SC-H and 6005SC-H are designated for STEP capacity
control.
The capacity shall be 100%, 75%, 50% or 25% (except for 4005SC-H).
The capacity shall be 100%, 75%, 50% or 33% (only for 4005SC-H).
- 4Models of 4005SC-Z, 5005SC-Z and 6005SC-Z are designated for INFINITE capacity
control.
The capacity ranges between 100% and 25% (except for 4005SC-Z).
The capacity ranges between 100% and 33% (only for 4005SC-Z).
- Piping sizes show the external diameter of piping in mm, which is the size
of the flange that compressors are equipped with.
- The standard color is light green (Munsell Code 10G5/2). Other colors are
available upon request.
- The cooling capacity and the motor input are based on the following conditions:
- The overall dimensions and the net weight are subject to change depending
on order specifications.
- These Compressors should be installed indoors or in a location equivalent
to an indoor environment..