| 1. |
The compressors are driven by a two pole motor directly mounted on the compressor shaft. A rotation speed at 50Hz is 2,880 rpm and that at 60Hz is 3,470 rpm respectively at a rated voltage. |
| 2. |
Either refrigerant of R407C, R134a or R22 is applicable. Oil is charged in each compressor at the time of shipment. |
| 3. |
Models of 40ASC-H, 50ASC-H and 60ASC-H are designed for STEP capacity control system.
The capacity shall be set at either 100%, 75%, 50% or 15% (for all models). |
| 4. |
Models of 40ASC-Z, 50ASC-Z and 60ASC-Z are designed for INFINITE capacity controll system.
The capacity range is between 100% and 15% (for all models).
|
| 5. |
Piping sizes show the external diameter of pipe connection of pre-equipped flange in "mm". |
| 6. |
The standard color is light green (Munsell code 10G 5/2). Other colors are available upon request. |
| 7. |
The cooling capacity and the motor input are based on the following conditions, ARI Standard rating conditions for compressors used in Air Conditioners and Heat Pumps.
|
| 8. |
The overall dimensions and the net weight are subject to change depending on order specifications. |
| 9. |
These Compressors should be installed indoors or in a location equivalent to an indoor environment. |
| 1. |
The compressors are driven by two pole motors directly mounted on the compressors shaft, and with a rotation of 2,880 rpm for 50Hz and 3,470 rpm for 60Hz, at the rated voltage.
|
| 2. |
Refrigerant R22, R407C and R134a are applicable to these compressors. Oil is charged in these compressors at the time of shipment.
|
| 3. |
Models of 4005SC-H, 5005SC-H and 6005SC-H are designated for STEP capacity control.
The capacity shall be 100%, 75%, 50% or 25% (except for 4005SC-H).
The capacity shall be 100%, 75%, 50% or 33% (only for 4005SC-H).
|
| 4. |
4Models of 4005SC-Z, 5005SC-Z and 6005SC-Z are designated for INFINITE capacity control.
The capacity ranges between 100% and 25% (except for 4005SC-Z).
The capacity ranges between 100% and 33% (only for 4005SC-Z). |
| 5. |
Piping sizes show the external diameter of piping in mm, which is the size of the flange that compressors are equipped with.
|
| 6. |
The standard color is light green (Munsell Code 10G5/2). Other colors are available upon request.
|
| 7. |
The cooling capacity and the motor input are based on the following conditions: |
| 8. |
The overall dimensions and the net weight are subject to change depending on order specifications. |
| 9. |
These Compressors should be installed indoors or in a location equivalent to an indoor environment.. |