Hitachi continues to propose unique product lines in order to meet demands for various types of air conditioning systems. The SET-FREE FSNM series is multi-split air conditioning system with a front-flow type fan, which combines the compactness and lightness of the UTOPIA series and the VRF function of the SET-FREE series (as of October 2008).
Comparison of HITACHI 10 HP class models
| Series | UTOPIA IVX DC Inverter |
SET-FREE FSNM | SET-FREE FS Series |
|
|---|---|---|---|---|
| Hitachi's multi-split system released 15 year ago | Hitachi's latest multi-split system | |||
| Type | Front-Flow Type | Front-Flow Type | Top-Flow Type | Top-Flow Type (FSN2 Series) |
| Refrigerant Charge | 7.8kg | 5.5kg | 17.5kg | 10.5kg |
| Floor Area | 0.429m2 | 0.429m2 | 1.225m2 | 0.896m2 |
| Net Weight | 170kg | 170kg | 345kg | 275kg |
| Actual Maximum Piping Length (Equivalent length) | 100m (120m) | 100m (120m) | 100m(125m) | 165m (190m) |
| Total Piping Length | 145m | 250m | 362m | 1,000m |
| Height Difference Between Indoor and Outdoor Units (Lowest outdoor unit) | 30m (20m) | 40m (30m) | 50m (40m) | 50m (40m) |
| Max. Number of Connectable Indoor Units | 4units | 10units | 8units | 16units |
| Capacity Ratio of Connected Indoor Unit *1 | 100% | 50~130% (8 and 10HP) 50~110% (12HP) *2 |
50~130% | 50~130% |
| Min. Capacity of Connectable Indoor Units | 2HP | 0.8HP | 1HP | 0.8HP |
Top-class Compact and Light Weight Design







The piping can be designed and constructed up to a maximum piping length of 100m. (total piping length: 250m)
New Type DC Inverter Scroll Compressor


Technology to Improve Heat Exchanger Performance
In the front-flow model, wind speed distribution is rendered uniform by making the direction of the wind flow to the fan and the heat exchanger the same. As a result, the performance of the heat exchanger is optimized and energy is saved.

Low Noise Technologies
The industry-leading low noise outdoor unit is realized by adopting the new model fin with low pressure loss.


The smooth rotating fan motor with low vibration reduces the noise generation.

Super High-stream fan of Φ544 mm cuts down the noise.

The draft resistence is reduced by 20%. Both high-efficiency and low noise operation are simultaneously satisfied.

Self-demand Control
A newly developed self-demand function has largely improved energy-saving effects. Since the current is self-detected and demand control performed automatically, no signal wiring work is required. Conventional demand control using demand signals is also available, and you can select various operations as required.

Wave Mode
Wave mode equipped to turn demand control ON and OFF alternately at intervals of about 20 min. or 10 min.While power is saved without fail, temperature changes are also minimized to maintain a comfortable room temperature.


The performance is the same regardless of the length of the refrigerant pipe.

Quickly senses air temperature difference to demonstrate proper performance.
Energy-saving operation without loss realized.
| Refrigirant (Number of models) |
Capacity Range [HP] | ||
|---|---|---|---|
8 |
10 |
12 |
|
| R410A (3 models) | |||