Centrifugal chillers, etc., are operated around the clock to generate chilled
water. In winter, air source heat pump and heat recovery type centrifugal chillers are used to generate
warm water. Because steam is generated so as to supply warm water, steam absorption chiller is also installed. |
 |
 |
 |
Specifications of chiller |
 |
 |
| Motor-driven centrifugal chiller |
1,000 RT 1 unit |
| Model |
HS-20C-ES |
| Chilled water temperature |
inlet 12, outlet 6 degree |
| Rated motor output |
700 kW |
| Heat recovery type centrifugal chiller |
1,000 RT 1 unit |
| Model |
HS-20C-ESD |
| Chilled water temperature |
inlet 12, outlet 6 degree |
| Warm water temperature |
inlet 40, outlet 47 degree |
| Rated motor output |
750 kW |
| Double effect steam absorption chiller |
400 RT 1 unit |
| Model |
HAU-W-500N |
| Chilled water temperature |
inlet 13, outlet 6 degree |
| Steam inlet pressure |
8 kgf/cm2G |
| Heat pump centrifugal chiller |
600 RT 1 unit |
| Model |
Hs-700/360H-AT |
| Chilled water temperature |
inlet 12, outlet 6 degree |
| Warm water temperature |
inlet 40, outlet 47 degree |
| Rated motor output |
450 kW, 300kW |
|
 |
 |
 |
 |
 |
 |
 |
1,000 RT centrifugal chiller |
400 RT double effect steam
absorpition chiller |
 |
|
|