Double effect steam absorption chillers are operated utilizing the waste
steam of gas turbine co-generation system. HITACHI, LTD., established works
of total air conditioning system of South-plant & North-plant. |
 |
 |
 |
Specifications of chiller |
 |
 |
| Double effect steam absorption chiller |
350 RT 2 unit |
| Model |
HAU-W-500SS |
| Chilled water temperature |
inlet 12.5, outlet 5.5 degree |
| Cooling water temperature |
inlet 32, outlet 38 degree |
| Steam inlet pressure |
8 kgf/cm2G |
| Double effect steam absorption chiller |
1,700 RT 4 unit |
| Model |
HAU-W-2240S |
| Chilled water temperature |
inlet 12.5, outlet 5.5 degree |
| Cooling water temperature |
inlet 32, outlet 38 degree |
| Steam inlet pressure |
8 kgf/cm2G |
|
 |
 |
 |
 |
 |
 |
2,000 RT double effect steam absorpition chiller |
 |
|
|