Heat supply of Kanagawa Science Park was planned so as to flexibly cope with the
frequently changing demand of various reseatch and development facilities, such as test facilities, research
laboratories, training facilities and hotels. The heat source uses electricity as well as city gas to operate
absorption chillers, centrifugal chillers, etc. Of the absorption refrigerating machines, two are gas direct
fired absorption chiller-heater units and operated in cooling mode in summer while in heating mode in winter. |
 |
 |
 |
Specifications of chiller |
 |
 |
| Double effect steam absorption chiller |
1,000 RT 2 unit |
| Model |
HAU-W-1000HSI |
| Chilled water temperature |
inlet 13, outlet 7 degree |
| Steam inlet pressure |
8 kgf/cm2G |
| Gas direct fired sbsorption chiller-heater |
800 RT 1 unit |
| Model |
HAU-FG-800HS |
| Gas direct fired sbsorption chiller-heater |
1,000 RT 1 unit |
| Model |
HAU-FG-1000HS |
| Chilled water temperature |
inlet 13, outlet 7 degree |
| Warm water temperature |
inlet 40, outlet 46 degree |
| Fuel |
city gas (13A) |
| Motor-driven centrifugal chiller |
400 RT 1 unit |
| Model |
HS-400S |
| Chilled water temperature |
inlet 13, outlet 7 degree |
| Rated motor output |
260 kW |
|
 |
 |
 |
 |
 |
 |
1,000 RT double effect steam absorption chiller (both right and
left side units) |
 |
 |
 |
 |
 |
 |
1,000 RT gas direct fired absoption water cooling/heating unit |
800 RT gas direct fired absorption chiller-heater unit |
400 RT motor-driven centrifugal chiller |
 |
|
|