Hitachi Appliances, Inc.
Hanedakuko Okiaitenkai-tou District [New Tokyo Airport Area]
HITACHI, LTD., delivered 3 units of world-largest 2,500 RT steam absorption chiller. The increased cooling water outlet temperature (40 degree) effectively reduces the size of cooling tower as well as the required power of cooling water pump. A compactly designed chiller even though refrigerant capacity is increased, keeping the overall height to only 3.5 m.
Features Specifications of chiller
Double effect steam absorption chiller 2,500 RT 3 unit
Model HAU-W-2800S
Chilled water temperature inlet 13, outlet 6 degree
Cooling water temperature inlet 32, outlet 40 degree
Steam inlet pressure 8 kgf/cm2G
2,500 RT double effect steam absorption chiller
2,500 RT double effect steam absorption chiller